Description
Dry bulb temperature sensor, 4 or 20mA, for referential enthalpy control with Honeywell solid state economizers.
C7660 selectable temperature sensors are used with W7212 and W7459 economizers for referential dry bulb changeover.
Features & Benefits:
- Senses temperature of outdoor air and provides a signal to economizer control with OK or not OK to economize
- Selectable DIP switch provides eight change over temperature options
- When temperature of outdoor air is below change over temperature, the outdoor air damper is opened to reduce the cooling load in the building
- Provides 4 mA or 20 mA output signal to economizer control; At 4 mA not OK to economize, at 20 mA OK to economize
- Highly accurate microprocessor control
- Sensor is enclosed in a rugged, corrosion-resistant plastic case
- Replaces C7650 temperature sensors and the control function of temperature change over in the economizer control
Certifications:
- UL Flammability Rating: UL94-5V